|
ASHRAE 15-2001 and Mechanical and Fire Code
Requirements For the Monitoring of Leaked Refrigerant
The requirements for the monitoring
for Leaked Refrigerants within an HVAC or Refrigeration Machinery Room typically are:
1. Each
refrigerating machinery room shall contain a detector for refrigerant gas or
vapor to be located in an area where refrigerant from a leak will concentrate
Genesis International offers two unique sensing
technologies for the detection of leaked refrigerant:
The SHERLOCKTM
Infra-Red Refrigerant Gas Sensor
The SHERLOCKTM
Solid State Refrigerant Gas Sensor
Each sensing technology is designed to be placed
into the area where refrigerant from a leak will likely concentrate. The
sensors produce an analog signal that can be monitored by a SHERLOCKTM
Refrigerant Gas Monitoring Panel or by a control system supplied by others.
2. The
refrigerant gas detection system shall:
- Actuate
an alarm
-
Activate mechanical ventilation
-
Shutdown any combustion process or "high heat" producing devices.
The SHERLOCKTM
Refrigerant Gas Monitoring Panels were designed to monitor the analog signal
from either the SHERLOCKTM
Infra-Red Refrigerant Gas Sensor,
the SHERLOCKTM
Solid State Refrigerant Gas Sensor or
analog output producing refrigerant gas sensors manufactured by other suppliers.
Each panel is designed to activate relay outputs that can be connected to
activate and control a number of alarming circuits, to include:
- Audio and Visual Alarms
- Mechanical Ventilation
- The Shutdown of mechanical
devices such as chillers, boilers, pumps, etc....
- Interface with Building Alarm
Systems
The SHERLOCKTM
Refrigerant Gas Monitoring Panels are available with an optional Analog Output
Module and Zone Isolation Relay modules.
Analog Output Module - This option is currently available only for the
Sherlock 102, 204, 404 or 804 Control Systems. The AO option provides one
analog output circuit for each sensor. This output produces a configurable
signal that will correspond its assigned refrigerant detection sensor's signal.
Output signal can be configured to be either 4-20ma (250Ohm maximum), 0-5VDC or
0-10VDC.
Zone Isolation Relay Modules - This options provides an additional one
or two (Model specific) relays for each sensor monitored. The Zone
Isolation Relays will activate its assigned sensor exceeds the relay's
programmed alarm level.
3. Alarming Requirements
- Audible
and Visual Alarm - Visible throughout the entire space, loud enough to be heard
over the noise of the mechanical equipment
- Located
inside the machinery room to facilitate evacuation
- Located
outside each entrance to the refrigerating machinery room to prevent access into
a hazardous environment.
- Alarms
are to be manually reset only, with the reset device located outside of the
machinery room.
Genesis International offers a substantial array of
products for the enunciating of a refrigerant leaks alarm. See
Alarm Indication
Equipment
4. Emergency Purge
Ventilation Requirements. The Refrigerant Leak Monitoring shall activate
an emergency ventilation system to evacuate the air from within the machinery
room
The SHERLOCKTM
Refrigerant Gas Monitoring Panels provide alarm relay contacts that can be
connected to activate Emergency Purge Ventilation equipment. The
SHERLOCK prevents the short cycling of the ventilation system by either
requiring manual reset of the alarm relay or by offering a reset delay for the
shutdown of the ventilation system. This reset delay will provide a
minimum runtime for the ventilation fan before it shuts off.
5. Combustion "High Heat"
Producing Device Shutdown Requirements. Should any device that produces
either a surface temperature of greater than 800 deg F or have an open flame
have the ability to come into contact with refrigerant leaked into the machinery
room, that device shall be shutdown upon the activation of the Refrigerant Leak
Monitor Alarms.
The SHERLOCKTM
Refrigerant Gas Monitoring Panels provide alarm relay contacts that can be
connected to shutdown any combustion systems or high heat producing appliances.
6. Providing of Remote
Controls for the Ventilation and Mechanical Equipment. Many mechanical
codes and ASHRAE 15 are requiring a control station consisting of at least an
ON-OFF switch (a few codes specify "break glass type") be provide immediately outside of the machinery room. This
control station will:
-
Manually start the Ventilation System into the Emergency Purge CFM levels.
-
Manually shutdown all electrically energized devices within the machinery rooms,
excluding the Refrigerant Detection System and the Ventilation System.
-
Indication panel to show the operational status of the ventilation system.
This panel contains two indictor lights to show that the ventilation system is
either drawing air out of the machinery room (Flow) or is off or has failed (No
Flow).
Genesis International stocks a number of accessories
for the compliance of ANSI/ASHRAE 15-2001 and various Mechanical and Fire Codes.
Break Glass Switch - This switch is suitable for
meeting the requirements for manual control of the ventilation fan and for the
shutting down of the mechanical equipment
See
Alarm Indication
Equipment
|