Product Categories

Refrigerant Gas Monitoring Panels - Fixed Systems

Refrigerant Gas Monitoring - Portable Systems

Compressor Condensing Unit Control Panels

Condenser Control Panels

Evaporator - Room - Zone Control Panels

Air-Handler, Chiller, and Energy Management Control Panels

Sensors

Breathing Apparatus and Accessories

Alarm Indication Equipment

Remote Monitoring and Communications

OEM - Original Manufactured Equipment

Wizard Single Compressor Control System

ENCLOSURE  MODEL        NEMA/IP     ELECTRICAL     POLLUTION

        #            RATING       CATEGORY      PROTECTION

    WSCC               1                    II                        2  WSCC-4       4x / Ip67                II                        3

WSCC-PM             1                    II                        2

NEMA 1 Compliant Enclosure - This enclosure is intended for indoor use only primarily to provide a degree of protection against contact with the enclosed equipment. The enclosure is not designed to provide protection from water or to be placed in a hazardous environment. Mount only in Pollution Level 2 environments, ie. environmentally controlled offices, control rooms, or environmentally controlled machine rooms.DIMENSIONS    12"H x 9.25"W x 5.0"D Nema 1

 

NEMA 4X Compliant Enclosure - This enclosure is intended for either indoor or outdoor use, 0 to 50 °C, to provide a degree of protection against corrosion, windblown dust and rain, splashing water, and hose directed water.DIMENSIONS   14"H x 15"D x 8.2 "D Nema 4X

 

NEMA 1 Panel Mount Option - The control and display assemblies must be suitably mounted in an enclosure. The Faceplate may be surface mounted onto a Nema 1 enclosure. The IO Board Assembly must be mounted within an enclosure providing at least Nema 1 protection.

 

POWER             90 to 250VAC, 50/60 Hz, 2.5 Amps

INPUTS (All inputs use unpluggable screw terminals)                          Three (3) Pressure Transducers                                  Suction Pressure, 14.7in Vacuum to 100psig or 0 to 200psig                                  Oil Pressure, 0 - 200 psig                                  Head Pressure, 0 - 500 psig                          Three (3) RTD Temperature Sensors                                  Discharge Temperature, 2-wire thermistor, -40 to 150°F                                  Head Temperature, 2-wire Thermistor, -40 to 350 °F

                                 Oil Temperature, 2-wire thermistor, -40 to 350 °F

                         One (1) Dry Contact                                 System Standby OUTPUTS          Eight SPDT, 1 Form C, 250VAC, 3.15Amp relays OPERATING TEMPERATURE     20ºF - 120ºF

OPERATING HUMIDITY              20% - 90% RH, non- condensing ALARMS             System Alarms (1 relay)

                                 Suction High/Low                                  Oil Pressure Low                                  Head Pressure High/Low                                  Discharge Temp High/Low                                  Oil Temperature High/Low                                  Head Temperature High/Low                                  System Internal Alarm Conditions

DISPLAY             2 lines by 20 characters Alphanumeric LCD with back light KEYPAD              5 tactile key switches:  Scroll up, Scroll down, Select/Change, Exit, Force Defrost Start/Advance ALARM INDICATORS       LCD DISPLAY          Name, description, and current reading of alarming sensor       BUZZER                  Piezo-electric, 90db @10ft, silenceable      STROBE LIGHT (Optional)       Mounted on top of the housing, activates during any alarm condition.

 

 

Genesis International, Inc. reserves the right to change product specifications and availability without notice.

Contact a factory representative for additional information on this and any other products.