Product Categories

Refrigerant Gas Monitoring Panels - Fixed Systems

Refrigerant Gas Monitoring - Portable Systems

Compressor Condensing Unit Control Panels

Condenser Control Panels

Evaporator - Room - Zone Control Panels

Air-Handler, Chiller, and Energy Management Control Panels

Sensors

Breathing Apparatus and Accessories

Alarm Indication Equipment

Remote Monitoring and Communications

OEM - Original Manufactured Equipment

 

 

EPC 2000 Multiplex Parallel Rack Control

  • An all electronic control system that can control the compressors, condenser and defrost of a multiplex refrigeration rack

Click for Specifications

EPC2000 Product Page

Condenser Control

The EPC-2000 can operate a remote condenser with up to seven independent fan banks and one split condenser valve. The EPC-2000 can monitor the head pressure, ambient temperature, liquid drop leg temperature, a gas defrost status signal, and a heat reclaim status signal.

Sequential Staging--The EPC-2000 will sequentially stage the fan banks in the FILO format (first on last off). The fan bank closest to the condenser input manifold should always be assigned as the first, or primary, fan bank. The EPC will keep the first fan bank running nearly constantly to prevent expansion and contraction at the pipe and tube sheet joints.

Parallel Fan Bank Control--If the condenser has a primary side and a secondary, or split, side with fans on each side, both sets of fans should be controlled by the same condenser relay. The contactor power for the split fans should also be controlled by the Split Condenser Relay on the EPC Condenser Board.

Fixed Head Pressure Control--The EPC-2000 can stage the condenser fan banks based upon a fixed head pressure setpoint.

Floating Head Pressure Control--The EPC-2000 can stage the condenser fan banks based upon the temperature of the liquid drop leg temperature and ambient temperature. The EPC-2000 will maintain the liquid at the Ambient Sub Cooled Refrigerant Setpoint.

Split Condenser--The EPC-2000 will attempt to maintain the condenser in its smallest configuration. If the EPC-2000 can maintain the head pressure while in the "split condenser" mode even though the ambient temperature is above 70 °F, the EPC will do so. The EPC-2000 will lock into the Split mode when the ambient temperature is below a setable ambient temperature Setpoint. The EPC will only come out of split condenser when the following occurs:

  1. The head pressure reaches 85% of the high head pressure alarm level.

  2. The maximum number of fan banks are operating and the head pressure continues to rise.

When the EPC-2000 goes into Split Condenser, the EPC closes the Split Condenser Relay, closing the split valve and shutting power off to the split side fans, and will automatically double the number of fan banks previously being run. When the EPC-2000 comes out of Split, the Split relay will open, and the number of fan banks being run will be halved.

Ambient Temperature Compensation of the Fan Start/Stop Timing--The EPC will adjust the start and stop timing of the condenser fans based upon the ambient temperature. The EPC will more than likely start fans faster when the ambient temperature is warmer and will stop fans faster when the ambient temperature is cooler.

Minimum Head Pressure During Heat Reclaim--When the EPC-2000 detects the Heat Reclaim relay is energized, the EPC will maintain a minimum head pressure by reducing the number of fan banks active and adjusting the compressor staging.

Minimum Head Pressure During Gas Defrost--The EPC-2000 will maintain a minimum head pressure by reducing the number of fan banks active and slowing the compressor staging.

Fan Staging After Gas Defrost--The EPC-2000 will adjust the fan control algorithm immediately following the end of a gas defrost. The EPC will anticipate the increase of load due to the recovery time of the defrost circuit.

Parallel Mechanical Backups--Backup pressure controllers or thermostats are wired in parallel with the EPC Condenser Control Relays with their power supply circuitry wired through the Condenser Switchback Relay. If the EPC were to fail, the Condenser Switchback Relay will de-energize, supplying power to the backup controls. The backup controls may be set as closely to the Head Pressure Setpoint as possible.

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Genesis International, Inc. reserves the right to change product specifications and availability without notice.

Contact a factory representative for additional information on this and any other products.

Copyright © Genesis International Inc. All Rights Reserved.