CF 1000
Condenser Fan Control

CONTROL SYSTEM
-
Setpoints and system
configuration stored within
serial EEPROM
-
Clock is Y2K compliant, leap
year compatible until year
2100 and is battery backed
for a minimum of 5 years
-
Menu driven controls with all
operating sequences and control
algorithms included.
-
The control has non-volatile
program memory and a battery
backed clock in the event of a power outage.
-
All programmable options are
installed via a Yes/No or
Installed/Not-installed question.
-
Keypad
-- Front Panel accessible with 4
tactile key switches.
-
Key Assignments
--Up, Down, Enter/Select, Exit.
-
Display
-- 1 line by 10 character Vacuum
Fluorescent Display (FIP).
Display will shut off after 30
minutes. It will turn on when any
key is pressed.
-
Power
--120/208/240VAC, 50/60HZ 40VA
-
Housing --
Metal Cabinet, NEMA 1
INPUTS
-
Discharge, or Head,
Pressure
-
Liquid Line Drop Leg
Temperature Sensor
-
Ambient Temperature
Sensor
-
Heat Reclaim Relay
Status
-
Gas Defrost Status
Pressure Transducers -- 3-wire,
V+ Signal Ground, analog 1 to 6 VDC
signal Ranges--0 to 100 PSI, 0 to 200
PSI, 0 to 500 PSI
Temperature Sensors -- 2-wire,
Microprocessor based, -40 to 158 °F
Digital Inputs -- All
Digital Inputs are low voltage, 5VDC open
or close signal inputs. All digital
signal sources are non-polarity specific.
OUTPUTS--Control
Relays - 7 Relays
|