W3LL 3 Zone Lead/Lag Control System

W3LL

MODEL          NEMA/IP       ELECTRICAL     POLLUTION

      #               RATING       CATEGORY       PROTECTION

   W3LL               1                      II                       2

 W3LL-4          4X/IP67                II                       3

ENCLOSURE

NEMA 1 Compliant Enclosure - This enclosure is intended for indoor use only primarily to provide a degree of protection against contact with the enclosed equipment. The enclosure is not designed to provide protection from water or to be placed in a hazardous environment. Mount only in Pollution Level 2 environments, i.e.. Environmentally controlled offices, control rooms, or environmentally controlled machine rooms.

                              12.5"H x 8.75"W x 3.2"D - NEMA 1 Long

NEMA 4X Compliant Enclosure - This enclosure is intended for either indoor or outdoor use, 0 to 50 °C, to provide a degree of protection against corrosion, windblown dust and rain, splashing water, and hose directed water.

                               14"H x 12"W x 7"D - NEMA 4X

POWER               90 to 250VAC, 50/60 Hz, 1.0 Amps

INPUTS                One (1) Thermistor Temperature Sensors

                               One (1) SHERLOCK Refrigerant Gas Sensor - CMOS or IR

                               One (1) Door Ajar Magnetic Contact Switch

                               One (1) Entrapment Push button switch

                               Three (3) Defrost Termination switch - one per system

                               One (1) Maximum Cooling switch

OUTPUTS           Control and Alarm Relays.  1 Form C SPDT, 250 VAC, 3.15 Amp slow blow fuse on the common leg.

                                       System Alarms, Refrigerant Leak Alarms, Two Liquid Line Solenoid

                               Fan and Defrost Relays.   (standard)  1 Form C SPDT, 250 VAC, 3.15 Amp slow blow fuse on the common leg.

                                                                             (optional)   2 Form A SPST, 250 VAC, 30Amp, two isolated circuits

OPERATING TEMPERATURE     45ºF - 120ºF

OPERATING HUMIDITY               30% - 90% RH, non-condensing

ALARMS             System Alarms (2 relays)

                                       DoorAjar, Entrapment, Low Temperature, High Temperature

                               Refrigerant Gas Leak Alarm

                                       Two alarm levels (2 SPDT Relays per level)

                               On Board driver circuitry to energize one external Audio/Visual device (12VDC, 1A)

                               On Board driver circuitry to energize one panel mounted Strobe Light (Factory Option)

                               On Board Piezo Electric Beeper (90 dBA at 10 ft)

DISPLAY             2 lines by 16 characters Alphanumeric LCD with back light

KEYPAD              5 tactile key switches:  Scroll up, Scroll down, Select/Change, Exit, Alarm Silence/Clear

ALARM INDICATORS

      LCD DISPLAY          Cause of Alarming

      BUZZER                    Piezo-electric, 90db @10ft, silenceable

      STROBE LIGHT (Optional)       Mounted on top of the housing, activates during any alarm condition.

CONTROL SYSTEM

Microprocessor based. Program logic stored within non-volatile Flash EPROM memory. Set points and system configuration stored within EEPROM with at least 10 years storage life. Logged Data and time clock is stored on the memory chip with backup power.

Menu driven controls with all operating sequences and control algorithms included. The control has non-volatile program memory and a capacitor backed clock in the event of power outage. All programmable options are installed via a "Yes" or "No" type question.

 