| Features
The Wizard Critical Products Control System is designed
to control the room or zone temperatures and the
evaporator operations for critical product refrigerated
storage rooms. The Wizard performs the functions of the
following independent control systems:
Temperature Control
Defrost Clock
Temperature Monitoring and Alarming
Refrigerant Gas Leak Monitor
System Shutdown
Temperature Recorder
Alarm System
The Wizard CPCS can be configured to operate as an
independent system, or as the controller of side of a
completely redundant system.
Temperature Control
Each Wizard comes with a temperature sensor for
monitoring or controlling the temperature in the
refrigerated room. The control monitors for both high
and low alarms each having its own programmed delay when
programmed. The Wizard will maintain the space
temperature by cycling the LLS based upon a Temperature
Setpoint and a plus/minus differential. The Wizard will
open the LLS when the temperature reaches T = Setpoint
minus Differential Value. The Wizard will close the LLS
when the temperature reaches T = Setpoint plus
Differential Value.
Defrost Control
The Wizard is an electronic control and time clock. The
time clock can operate up to 12 defrost cycles per day
with three separate defrost schedules as well as manual
defrost. The defrost can be either gas, electric or
off-time defrost. The Wizard will cycle all valves
necessary to perform a Hot Gas defrost of some of the
more complex refrigeration systems.
During a defrost cycle the Wizard will sequence the
following as required:
Liquid Line Solenoid
Evaporator Fan Motor Starter
Defrost Control Circuitry
Hot Gas Valve
Electric Defrost Contactor
Water Valves
Defrost Features
Daily Schedules.
The control has three unique
defrost schedules: Weekday (Monday - Friday), Saturday
and Sunday.
Defrost Cycle Steps.
The Wizard CPCS allows the
user to program the lengths of the following defrost
cycles:
Pump Down
Defrost
Drip Cycle
Fan Start Delay.
Automatically adjusts time for daylight savings.
The Wizard can be set to automatically change the
clock for day light savings or can be set not to change
if the facility is in states where daylight savings is
not observed. The Daylight Savings Schedule is set
through 2020.
Can schedule up to 12 defrost cycles per day.
The Wizard can be programmed to run up to 12 defrost
cycles per day. The control will automatically space out
each cycle evenly or allow the user to program the start
times.
Gas, Electric, or Air defrosts.
The Wizard can
operate defrost circuits that are Off-time, Hot Gas, or
Electric. Steps that are not used can be set to 0
minutes, and the controller will skip over them to the
next step.
Manually Activated Force Defrost Input
The
Wizard has a digital input that forces the control into
the defrost cycle. This input can be used to activate
the system for an additional defrost cycle, or with the
"Number of Cycles per Day" set to zero, the input can be
wired to a gang defrost clock and a number of Wizards
can be staged evenly or to a frost sensor and the Wizard
will defrost only when necessary.
Defrost Termination.
Any one of the following functions will
terminate the Main Defrost Cycle:
Clicks-On Thermodisk (Dry Contact).
Suction Pressure Switch (Dry Contact).
Termination Temperature Sensor.
Time.
Defrost Termination Log.
The Wizard has a
"Defrost Log" that records the duration of the previous
10 defrost cycle Defrost stages. This log can be used to
determine whether the current defrost setup is operating
efficiently or whether adjustments need to be made
Alarm Panel
The Wizard can monitor two independent temperature
sensors, the Temperature Control Sensor and the Defrost
Termination Sensor. The Wizard will produce an alarm
signal based upon a number of additional alarm
conditions.
Temperature Alarm -- This alarm is based upon the
reading produced by the sensor used for temperature
control. All alarming is disabled during defrost. Once
the Wizard controller returns to normal refrigeration,
the alarm delays will begin as if the sensor has just
exceeded the alarm conditions.
The Wizard will activate three independent alarm schemes
based upon this sensor:
High Temperature Level One, "Alert" Level
High Temperature Level Two, "Action" Level
Low Temperature Alarm Level.
Defrost Termination / Coil Recovery Alarm --
The
Defrost Termination sensor consists of the sensor used
by the Wizard to terminate the defrost cycle based upon
the coil temperature. Should this temperature read above
the setpoint level of the termination setpoint for over
30 minutes, the Wizard will activate its systems alarms.
Termination Temperature High Alarm.
The Wizard
will activate alarms if the termination Click-On or
the Termination Temperature does not recover within 30
minutes. This function shall activate the control’s
"System Alarm Relay".
Door Open Alarm --
The Wizard can monitor a Normally
Open Dry Contact Door Switch. This switch will indicate
whether the door is open or closed. A user definable
alarm delay is set and when the door is left upon for a
duration exceeding this delay, the Wizard will activate
the System Alarm Scheme.
Door Open Log -- The Wizard has a timer log that
counts the total amount of time that a door is open over
a 24 hour period. This log is retain for a period of 10
days. At any time, a user can access this log and
determine the amount of time that the walkin door is
open.
Compressor Failure Alarm --
The Wizard can monitor a
Normally Open Dry Contact Compressor Proofing Switch
provided by the condensing unit manufacturer. This
switch will indicate whether the compressor is on,
running, or off. When the Wizard calls for
refrigeration, the unit will begin a timer. If the
compressor proofing switch does not indicate a run
signal after a user definable delay, the Wizard will
activate the System Alarm Scheme.
Alarm Signals.
The Wizard has a standard, on board
90 dBA buzzer that will sound whenever the unit goes
into an alarm condition. Status LEDs will indicate which
alarm condition is active and the LCD Display will
display the specific alarm conditions.
Optional Strobe Light --
The Wizard CPCS has
an optional factory mounted strobe light that will
activate under all alarm conditions.
Refrigeration Leak
Monitoring.
The Wizard makes any refrigerated room Uniform
Mechanical Code Compliant with the addition of a
Sherlock Refrigerant Sensor. The Wizard will activate
alarms based upon two alarm levels. At the first alarm
level, the Wizard will activate the Gas Leak Level One
Alarm Relay, activating any alarm notification system
connected to the Wizard. At the second alarm level, the
Wizard will activate the Gas Leak Level Two Alarm relay,
activating additional alarm indication equipment and any
additional safety procedures as required by local codes.
The Wizard gives the user an option to pump down, then
isolate the evaporator coil should the leak
concentration exceed level two.
Gas Leak Sensors
The Sherlock Refrigerant Gas Sensor acts as an analog
signal generating sensor when connected to the control
module via a discrete, three conductor cable. The sensor
can be mounted up to 800 feet away in locations where
leaked refrigerant is likely to concentrate.
Sensors are available in specific configurations that
detect certain refrigerant gases.
Alarm Level Settings
The Wizard allows you to set two unique Alarm Setpoints
for the refrigerant gas sensor throughout its operating
range. When an Alarm Setpoint is exceeded, a
corresponding alarm relay is activated Each Alarm
Setpoint has a programable Alarm Delay, 1 to 120
minutes. The sensor reading is required to exceed an
Alarm Setpoint for the programmed amount of time before
the control activates the corresponding alarm relay
contacts. For example, if the Alarm Setpoint is 200 and
the Alarm Delay is five minutes, the control will enter
an alarm condition only if the sensor detects a level of
200 or higher for more than five minutes.
The Wizard has a programable option that will pump down
and isolate the coil when the Sherlock senosr reading
exceeds the Alarm Level 2 Alarm Setpoint.
Shutdown (Standby)
Some refrigerated facilities need to be placed into
Shutdown or Standby at certain times, whether they are a
seasonal facility (i.e. only stores produce during the
harvest season), require maintenance or cleaning, or a
production room where the room is not used during the
overnight hours.
Another use of the Shutdown procedures is when a
refrigerant leak is detected within the refrigerated
space. y connecting the Dry Contact Input #6 on the
Wizard IO Board to a refrigerant gas monitoring system
(by others) or another Wizard configured to monitor for
refrigerant leaks, the Wizard can properly isolate an
evaporator coil during an alarm condition
Standby Control Method -
The Control Method
determines the action necessary to initiate and
terminate Standby/Shutdown. Standby can be controlled by
any one of the following four methods:
Dry Contact Closure - Should a contact close
across Input # 6 on the Wizard Input Board, the Wizard
will go into Standby/Shutdown. The control will remain
in Standby/Shutdown until the contact opens.
Manually Forced - The control will go into
its Standby/Shutdown mode when the "Standby Mode" is
changed to "Man", or manual. The control will remain in
Standby/Shutdown until the "Standby Mode" is changed
back to "Norm". See Below.
Daily Schedule - If the "Standby Mode" is
set to "Sch", the Wizard will go into Standby/Shutdown
at the same time daily. This schedule will remain active
until the "Standby Mode" is changed back to "Norm".
Gencom Communications Interface - The
Wizard Control Panels within a facility can be placed
into Standby/Shutdown via Gencom Communications System.
From a computer panel, the operator can force all or
some of the Wizard Panels into Standby/Shutdown. This
operation will internally change the "Standby Mode" from
"Norm" to "Man". The controllers will return to normal
either when the operator resets the Standby Flag or when
the "Standby Mode" is reset to "Norm" within the Standby
Ctl Menu.
Fans Run During Standby -
The option of whether to
shut off the fans when the evaporator is shutdown.
Refrigerant Leak Monitoring during Standby -
During
cleaning of a process room, the temperature and humidity
of the room can increase dramatically. These increases
may cause false alarms with the leak alarms. This
parameter gives the operator an option of continuing to
monitor for refrigerant leaks during shutdown.
Note: This parameter is visible only when the Wizard
is configured for Leak Monitoring.
Temperature Data Logging
The Wizard will record 1500
temperature log entries into its internal memory. The
Logging Interval can be set from 1 minute to 120
minutes. This information is retrievable via the front
display or with the GenCom for Windows software package.
With the optional GenCom Communication Kit the Wizard
can be operated remotely. The GenCom Kit allows the user
to view and change the settings, view and respond to
alarm conditions, check and report the status of all of
the Wizard at the site and place any of the controls
into manual defrost. One kit can operate up to 250
Genesis controls in one location. If the user has the
Premium Model, GenCom can be used to graph the data log.
To read this stored data, the facility must have a
GenCom Communications Network installed and connected to
either a modem or directly to a computer. The computer
operator can then download the data log, print the
graphs of the logged data, and store this data either on
the computer hard/floppy disk or print the data in a
table format.
Remote Communications
GenCom Communications allows the computer operator to
access the controllers within a facility via a PC. All
control programming and logging functions are accessible
and can be set or changed from the computer. The user
can view all text and data logs, make programming
changes to the controller, initiate defrost cycles, and
investigate alarm conditions. |