The Wizard Critical Products Control System is compliant with ASHRAE 15-1994 and the UNIFORM MECHANICAL CODE requirements for refrigerant gas monitoring.

ENCLOSURE

 

  MODEL           NEMA/IP      ELECTRICAL     POLLUTION

        #               RATING       CATEGORY      PROTECTION

 WCPCS                1                    II                        2

WCPCS-4       4x / Ip67                II                        3

 WEC-PM              1                     II                        2

 

NEMA 1 Compliant Enclosure - This enclosure is intended for indoor use only primarily to provide a degree of protection against contact with the enclosed equipment. The enclosure is not designed to provide protection from water or to be placed in a hazardous environment. Mount only in Pollution Level 2 environments, ie. environmentally controlled offices, control rooms, or environmentally controlled machine rooms.

DIMENSIONS    12"H x 9.25"W x 5.25"D Nema 1

 

NEMA 4X Compliant Enclosure - This enclosure is intended for either indoor or outdoor use, 0 to 50 °C, to provide a degree of protection against corrosion, windblown dust and rain, splashing water, and hose directed water.

DIMENSIONS    14"H x 12"D x 7"D Nema 4X

 

NEMA 1 Panel Mount Option - The control and display assemblies must be suitably mounted in an enclosure. The Faceplate may be surface mounted onto a Nema 1 enclosure. The IO Board Assembly must be mounted within an enclosure providing at least Nema 1 protection.

 

DIMENSIONS    10.2"H x 8.5" W x 2"D PM Faceplate

                              10.6"H x 8.5"W x 3"D PM Backplate

 

POWER               90 to 250VAC, 50/60 Hz, 1.0 Amps

INPUTS               One (1) RTD Temperature Sensors

                              One Dual Use Thermistor Temperature Sensor or Dry Contact Defrost Status

                              One (1) SHERLOCK sensor Cmos or IR

                              Five dry contacts -- Force Defrost, Shutdown, Control Status, Door Alarm, Compressor Proofing.

OUTPUTS           Thirteen SPDT, 1 Form C, 250VAC, 3.15Amp relays

OPERATING TEMPERATURE     45ºF - 99ºF

OPERATING HUMIDITY               30% - 90% RH, non- condensing

ALARMS             Temperature Alarms (2 relays)

                                     High Alarm Level 1

                                     High Alarm Level 2

                               System Alarm (1 relay)

                                     Compressor Proofing

                                     Low Temperature

                                     Door Open

                                     Termination Failure / Coil Recovery

                                     Refrigerant Gas Leak Alarm

                               Two alarm levels (2 SPDT Relays per level)

                               Alarm Company - Control Alarm Status Relay

                                     Relay active during all alarm conditions

DISPLAY             2 lines by 20 characters Alphanumeric LCD with back light

                               Alarm Indication LED -- indicates active alarm

                               Evaporator Control Status LEDS -- indicates Control Operating Status of Evaporator Controls Circuits

KEYPAD              5 tactile key switches:  Scroll up, Scroll down, Select/Change, Exit, Force Defrost Start/Advance

ALARM INDICATORS

      LCD DISPLAY          Name, description, and current reading of alarming sensor

      BUZZER                    Piezo-electric, 90db @10ft, silenceable

      STATUS LED            Two on front panel of control.

                                            Indicates alarm status of the System Alarm and the Refrigerant Leak Alarm