Product Categories

Refrigerant Gas Monitoring Panels - Fixed Systems

Refrigerant Gas Monitoring - Portable Systems

Compressor Condensing Unit Control Panels

Condenser Control Panels

Evaporator - Room - Zone Control Panels

Air-Handler, Chiller, and Energy Management Control Panels

Sensors

Breathing Apparatus and Accessories

Alarm Indication Equipment

Remote Monitoring and Communications

OEM - Original Manufactured Equipment

Wizard Defrost Control System

   

ENCLOSURE

 

  MODEL        NEMA/IP     ELECTRICAL     POLLUTION

        #            RATING       CATEGORY      PROTECTION

    WDC                1                  II                         2

  WDC-4       4x / Ip67               II                         3

WDC-PM            1                    II                         2

 

NEMA 1 Compliant Enclosure - This enclosure is intended for indoor use only primarily to provide a degree of protection against contact with the enclosed equipment. The enclosure is not designed to provide protection from water or to be placed in a hazardous environment. Mount only in Pollution Level 2 environments, ie. environmentally controlled offices, control rooms, or environmentally controlled machine rooms.

DIMENSIONS    12"H x 9.25"W x 5.25"D Nema 1

 

NEMA 4X Compliant Enclosure - This enclosure is intended for either indoor or outdoor use, 0 to 50 °C, to provide a degree of protection against corrosion, windblown dust and rain, splashing water, and hose directed water.

DIMENSIONS    14"H x 12"D x 7"D Nema 4X

 

NEMA 1 Panel Mount Option - The control and display assemblies must be suitably mounted in an enclosure. The Faceplate may be surface mounted onto a Nema 1 enclosure. The IO Board Assembly must be mounted within an enclosure providing at least Nema 1 protection.

DIMENSIONS    10.2"H x 8.5" W x 2"D PM Faceplate

                              10.6"H x 8.5"W x 3"D PM Backplate

POWER               90 to 250VAC, 50/60 Hz, 1.0 Amps

INPUTS               Two (2) RTD Temperature Sensors

                           One dry contacts -- Force Defrost, Shutdown, Load Shedding

OUTPUTS           Eight SPDT, 1 Form C, 250VAC, 3.15Amp relays

OPERATING TEMPERATURE     45ºF - 99ºF

OPERATING HUMIDITY               30% - 90% RH, non- condensing

ALARMS             System Alarms (2 relays)

                                       Low Temperature, High Temperature, Termination Failure / Coil Recovery

DISPLAY             2 lines by 20 characters Alphanumeric LCD with back light

                               Alarm Indication LED -- indicates active alarm

                               Evaporator Control Status LEDS -- indicates Control Operating Status of

                                   Evaporator Controls Circuits

KEYPAD              5 tactile key switches:  Scroll up, Scroll down, Select/Change, Exit, Force Defrost Start/Advance

ALARM INDICATORS

      LCD DISPLAY   Name, description, and current reading of alarming sensor

      BUZZER           Piezo-electric, 90db @10ft, silenceable

      STATUSLED     Two on front panel of control. Indicates alarm status of the System Alarm and the

                                  Refrigerant Leak Alarm

      STROBE LIGHT (Optional)       Mounted on top of the housing, activates during any alarm condition.

 

Genesis International, Inc. reserves the right to change product specifications and availability without notice.

Contact a factory representative for additional information on this and any other products.