           WIC                          WIC-30 Amp

MODEL         NEMA/IP     ELECTRICAL      POLLUTION

      #             RATING      CATEGORY       PROTECTION

   WIC              1                      II                        2

WIC-30            1                      II                         2

 WIC-4          4X/IP67               II                        3

WIC-30-4      4X/IP67               II                         3

 

ENCLOSURE

NEMA 1 Compliant Enclosure - This enclosure is intended for indoor use only primarily to provide a degree of protection against contact with the enclosed equipment. The enclosure is not designed to provide protection from water or to be placed in a hazardous environment. Mount only in Pollution Level 2 environments, i.e.. Environmentally controlled offices, control rooms, or environmentally controlled machine rooms.

                              7.4”H x 8”W x 3.2”D - NEMA 1

                              12.5"H x 8”W x 3.2”D - NEMA 1 30 Amp

NEMA 4X Compliant Enclosure - This enclosure is intended for either indoor or outdoor use, 0 to 50 °C, to provide a degree of protection against corrosion, windblown dust and rain, splashing water, and hose directed water.

                               14"H x 12"W x 7"D - NEMA 4X Long

POWER               90 to 250VAC, 50/60 Hz, 1.0 Amps

INPUTS                   One (1) Thermistor Temperature Sensors

                               One (1) SHERLOCK Refrigerant Gas Sensor - CMOS or IR

                               One (1) Defrost Termination switch

                               One (1) Door Ajar Magnetic Contact Switch

OUTPUTS           

       Control and Alarm Relays. 

                           1 Form C SPDT, 250 VAC, 3.15 Amp slow blow fuse on the common leg.

       Fan and Defrost Relays.   (standard)

                           1 Form C SPDT, 250 VAC, 3.15 Amp slow blow fuse on the common leg.

                           (optional)   2 Form A SPST, 250 VAC, 30Amp, two isolated circuits

       Relay Assignments

                               Liquid Line Solenoid

                               Evaporator Fan (Optional 30 Amp Relay)

                               Defrost             (Optional 30 Amp Relay)

                               System Alarm

                               System Alarm (Silencable)

                               Refrigerant Leak Level 1 (Silencable)

                               Refrigerant Leak Level 2 (Silencable)

                               Refrigerant Leak Level 2

OPERATING TEMPERATURE     45ºF - 100ºF

OPERATING HUMIDITY               30% - 90% RH, non- condensing

ALARMS             System Alarms (2 relays)

                                DoorAjar, Entrapment, Low Temperature, High Temperature

                            Refrigerant Gas Leak Alarm

                               Two alarm levels (2 SPDT Relays per level)

                            On Board Digital Output to energize one external Audio/Visual device-12VDC, 1A

                            On Board Digital Output to energize one panel mounted Strobe Light

                            On Board Piezo Electric Beeper (90 dBA at 10 ft)

 

DISPLAY             2 lines by 16 characters Alphanumeric LCD with back light

                           Status LEDs across the top of the control to display refrigeration status

                                Primary, Compressor On, In Defrost

KEYPAD              5 tactile key switches:

                                     Scroll up, Scroll down, Select/Change, Exit, Alarm Silence/Clear

ALARM INDICATORS

      LCD DISPLAY          Cause of Alarming

      STATUS LED           Type of Alarm - System or Refrigerant Gas Leak

      BUZZER                  Piezo-electric, 90db @10ft, silenceable

      STROBE LIGHT (Optional)       Mounted on top of the housing, activates during any alarm condition.

CONTROL SYSTEM

Microprocessor based. Program logic stored within non-volatile Flash EPROM memory. Set points and system configuration stored within EEPROM with at least 10 years storage life. Logged Data and time clock is stored on the memory chip with backup power.

Menu driven controls with all operating sequences and control algorithms included. The control has non-volatile program memory and a capacitor backed clock in the event of power outage. All programmable options are installed via a "Yes" or "No" type question.

 

Genesis International, Inc. reserves the right to change product specifications and availability without notice.