      WIM3 Walk-In Monitoring System - Three  Zones

 

 

 

MODEL       NEMA/IP       ELECTRICAL     POLLUTION

      #           RATING        CATEGORY       PROTECTION

  WIM3               1                  II                              2

 WIM3-4     4X/IP67                II                              3

NEMA 1 Compliant Enclosure - This enclosure is intended for indoor use only primarily to provide a degree of protection against contact with the enclosed equipment. The enclosure is not designed to provide protection from water or to be placed in a hazardous environment. Mount only in Pollution Level 2 environments, i.e.. Environmentally controlled offices, control rooms, or environmentally controlled machine rooms.

NEMA 4X Compliant Enclosure - This enclosure is intended for either indoor or outdoor use, 0 to 50 °C, to provide a degree of protection against corrosion, windblown dust and rain, splashing water, and hose directed water.

ENCLOSURE      7.4”H x 8”W x 3.2”D - NEMA 1

                               14"H x 12"W x 7"D - NEMA 4X

POWER               90 to 250VAC, 50/60 Hz, 1.0 Amps

INPUTS (Per Zone)              

                               One (1) Thermistor Temperature Sensors

                               One (1) SHERLOCK Refrigerant Gas Sensor - CMOS or IR

                             

            Shared      One (1) Door Ajar Magnetic Contact Switch

                               One (1) Entrapment Push button switch

OUTPUTS            Two SPDT, 1 Form C Relays with 250 VAC, 3.15 Amp fuses and spike suppressors

OPERATING TEMPERATURE     45ºF - 99ºF

OPERATING HUMIDITY               30% - 90% RH, non- condensing

ALARMS             System Alarms (2 relays)

                                       DoorAjar, Entrapment, Low Temperature, High Temperature

                               Refrigerant Gas Leak Alarm

                                       Two alarm levels (2 SPDT Relays per level)

                                       Three room specific relays (Liquid Line Solenoid Shutdown)

                               On Board driver circuitry to energize one external Audio/Visual device (12VDC, 1A)

                               On Board driver circuitry to energize one panel mounted Strobe Light (Factory Option)

                               On Board Piezo Electric Beeper (90 dBA at 10 ft)

                               On Board LED Alarm Indication Device (180 deg viewing angle)

DISPLAY             2 lines by 16 characters Alphanumeric LCD with back light

                               Alarm Indication LED -- indicates active alarm

KEYPAD              5 tactile key switches:  Scroll up, Scroll down, Select/Change, Exit, Alarm Silence/Clear

ALARM INDICATORS

      LCD DISPLAY          Cause of Alarming

      BUZZER                    Piezo-electric, 90db @10ft, silenceable

      FRONT PANEL LED LIGHT     Flashing red light when Control is in alarm

      STROBE LIGHT (Optional)       Mounted on top of the housing, activates during any alarm condition.

 