Product Categories

Refrigerant Gas Monitoring Panels - Fixed Systems

Refrigerant Gas Monitoring - Portable Systems

Compressor Condensing Unit Control Panels

Condenser Control Panels

Evaporator - Room - Zone Control Panels

Air-Handler, Chiller, and Energy Management Control Panels

Sensors

Breathing Apparatus and Accessories

Alarm Indication Equipment

Remote Monitoring and Communications

OEM - Original Manufactured Equipment

      WIM Walk-In Monitoring System

 

 

 

MODEL       NEMA/IP     ELECTRICAL     POLLUTION

      #           RATING      CATEGORY       PROTECTION

  WIM               1                   II                        2

 WIM-4        4X/IP67              II                        3

NEMA 1 Compliant Enclosure - This enclosure is intended for indoor use only primarily to provide a degree of protection against contact with the enclosed equipment. The enclosure is not designed to provide protection from water or to be placed in a hazardous environment. Mount only in Pollution Level 2 environments, i.e.. Environmentally controlled offices, control rooms, or environmentally controlled machine rooms.

NEMA 4X Compliant Enclosure - This enclosure is intended for either indoor or outdoor use, 0 to 50 °C, to provide a degree of protection against corrosion, windblown dust and rain, splashing water, and hose directed water.

ENCLOSURE            7.4”H x 8”W x 3.2”D - NEMA 1

                               14"H x 12"W x 7"D - NEMA 4X

POWER                   90 to 250VAC, 50/60 Hz, 1.0 Amps

INPUTS                   One (1) Thermistor Temperature Sensors

                               One (1) SHERLOCK Refrigerant Gas Sensor - CMOS or IR

                               One (1) Door Ajar Magnetic Contact Switch

                               One (1) Entrapment Push button switch

OUTPUTS                Two SPDT, 1 Form C Relays with 250 VAC, 3.15 Amp fuses and spike suppressors

OPERATING TEMPERATURE     45ºF - 99ºF

OPERATING HUMIDITY               30% - 90% RH, non- condensing

ALARMS                  System Alarms (2 relays)

                                       DoorAjar, Entrapment, Low Temperature, High Temperature

                               Refrigerant Gas Leak Alarm

                                       Two alarm levels (2 SPDT Relays per level)

                               On Board driver circuitry to energize one external Audio/Visual device (12VDC, 1A)

                               On Board driver circuitry to energize one panel mounted Strobe Light (Factory Option)

                               On Board Piezo Electric Beeper (90 dBA at 10 ft)

                               On Board LED Alarm Indication Device (180 deg viewing angle)

DISPLAY                 2 lines by 16 characters Alphanumeric LCD with back light

                               Alarm Indication LED -- indicates active alarm

KEYPAD                  5 tactile key switches:  Scroll up, Scroll down, Select/Change, Exit, Alarm Silence/Clear

ALARM INDICATORS

      LCD DISPLAY          Cause of Alarming

      BUZZER                    Piezo-electric, 90db @10ft, silenceable

      FRONT PANEL LED LIGHT     Flashing red light when Control is in alarm

      STROBE LIGHT (Optional)       Mounted on top of the housing, activates during any alarm condition.

 

Genesis International, Inc. reserves the right to change product specifications and availability without notice.

Contact a factory representative for additional information on this and any other products.

Copyright © Genesis International Inc. All Rights Reserved.