Product Categories

Refrigerant Gas Monitoring Panels - Fixed Systems

Refrigerant Gas Monitoring - Portable Systems

Compressor Condensing Unit Control Panels

Condenser Control Panels

Evaporator - Room - Zone Control Panels

Air-Handler, Chiller, and Energy Management Control Panels

Sensors

Breathing Apparatus and Accessories

Alarm Indication Equipment

Remote Monitoring and Communications

OEM - Original Manufactured Equipment

ComfortMiser Chiller Control System

ENCLOSURE

 

  MODEL        NEMA/IP     ELECTRICAL     POLLUTION

        #            RATING       CATEGORY      PROTECTION

    CMC               1                    II                        2

  CMC-4       4x / Ip67                II                        3

CMC-PM             1                    II                        2

 

NEMA 1 Compliant Enclosure - This enclosure is intended for indoor use only primarily to provide a degree of protection against contact with the enclosed equipment. The enclosure is not designed to provide protection from water or to be placed in a hazardous environment. Mount only in Pollution Level 2 environments, ie. environmentally controlled offices, control rooms, or environmentally controlled machine rooms.

DIMENSIONS    12"H x 9.25"W x 5.25"D Nema 1

 

NEMA 4X Compliant Enclosure - This enclosure is intended for either indoor or outdoor use, 0 to 50 °C, to provide a degree of protection against corrosion, windblown dust and rain, splashing water, and hose directed water.

DIMENSIONS    14"H x 12"D x 7"D Nema 4X

 

NEMA 1 Panel Mount Option - The control and display assemblies must be suitably mounted in an enclosure. The Faceplate may be surface mounted onto a Nema 1 enclosure. The IO Board Assembly must be mounted within an enclosure providing at least Nema 1 protection.

 

POWER             90 to 250VAC, 50/60 Hz, 1.0 Amps

INPUTS (All inputs use unpluggable screw terminals)

                         Four (4) Pressure Transducers

                                 Suction Pressure, 14.7in Vacuum to 100psig or 0 to 200psig

                                 Oil Pressure, 0 - 200 psig

                                 Head Pressure, 0 - 500 psig

                         Two (2) RTD Temperature Sensors

                                 Room 1 - Suction Pressure Reset (SPR) Temperature, 2-wire thermistor, -40 to 150°F

                                 Room 2 - Booster Compressor (Satellite) Temperature, 2-wire thermistor, -40 to 150°F

                         One (1) Dry Contact - Defrost Status (AC Shutdown)

                         One (1) Receiver Level Indicator - Configurable

                                 Digital, 4-20ma, voltage

OUTPUTS          Eight SPDT, 1 Form C, 250VAC, 3.15Amp relays

OPERATING TEMPERATURE     -20ºF - 120ºF

OPERATING HUMIDITY              20% - 90% RH, non- condensing

ALARMS             System Alarms (1 relay)

                                 Suction High/Low

                                 Oil Pressure Low

                                 Head Pressure High/Low

                                 Room Temp High/Low

                                 Receiver Level Low/Shutdown

                                 System Internal Alarm Conditions

DISPLAY             2 lines by 20 characters Alphanumeric LCD with back light

KEYPAD              5 tactile key switches:  Scroll up, Scroll down, Select/Change, Exit, Force Defrost Start/Advance

ALARM INDICATORS

      LCD DISPLAY          Name, description, and current reading of alarming sensor

      BUZZER                  Piezo-electric, 90db @10ft, silenceable

     STROBE LIGHT (Optional)       Mounted on top of the housing, activates during any alarm condition.

 

 