The
SHERLOCK Service Buddy Portable
Refrigerant Gas Monitor is for applications that require
a service technician to install or service refrigeration
equipment in an area that is not protected by a
refrigerant gas monitoring system. The portable unit
comes complete with a molded plastic carrying case, a
SHERLOCK 202 Control Module, a 95dB buzzer, two
refrigerant gas sensors and a 120V wallplug cord. All
alarm levels are factory programmed and user settable,
depending upon refrigerant
-
User definable alarm setpoints and
delays.
-
Simple 3-wire low voltage sensors -
PRE-WIRED.
-
Continuous monitoring of both
sensor.
-
Each alarm level has a two SPDT
relays.
-
Display constantly shows sensor
levels, alarm setpoints and current alarm status.
-
Capable of monitoring multiple
gases.
-
Effective monitoring range from 25
to 1000 PPM
-
Programmable setback timer and two
manual setback inputs to reduce false alarms.
-
Built in 95db alarm buzzer
-
Built-in 180 degree visible Alarm
LED
Refrigerant gas monitor provides
early warning for applications that require a service
technician to install or service equipment in an area
that is unprotected from refrigerant leaks.
Monitoring Panel
The Sherlock 102 Control
Module is a hard wired, permanently mounted electronic
control panel that is capable of monitoring the analog
output signal of one Sherlock Refrigerant Gas
Sensors or Oxygen Depletion
Sensors. The Control Module will activate four Form C
SPDT relay contacts based upon the programmed alarm
setpoints of each sensor. The relays are referred to as
K1, K2 for the first alarm level and K3, K4 for the
second alarm level. There is optional zone isolation
alarm relay (K5 & K6) for each Sensor. The Control
Module can be located in the area to be monitored, or in
a separate location, typically outside of the monitored
room.
Monitoring Points
Each monitoring point consists of an
analog signal generating sensor connected to the control
module via discrete, three conductor cable. Each sensor
can be mounted up to 1000 feet away in locations where
leaked refrigerant is likely to concentrate.
Ceramic Metal Oxide Semiconductor
(CMOS) or Solid State Sensor
Alarm Level Settings
The Sherlock 102 allows you to
set a unique Level 1 Alarm Setpoint and delay and Level
2 Alarm Setpoint and delay for each individual sensor.
When an Alarm Setpoint is exceeded, after the user set
delay, corresponding alarm relays are activated Each
Alarm Setpoint has a programmable Alarm Delay, 1 to 120
minutes. Sensor readings are required to exceed an Alarm
Setpoint for the programmed amount of time before the
control activates the corresponding alarm relay
contacts. For example, if the Alarm Setpoint is 200 and
the Alarm Delay is five minutes, the control will enter
an alarm condition only if the sensor detects a level of
200 or higher for more than five minutes.