Monitoring Panel
The Sherlock 102 Control
Module is a hard wired, permanently mounted electronic
control panel that is capable of monitoring the analog
output signal of one Sherlock Refrigerant Gas
Sensors or Oxygen Depletion
Sensors. The Control Module will activate four Form C
SPDT relay contacts based upon the programmed alarm
setpoints of each sensor. The relays are referred to as
K1, K2 for the first alarm level and K3, K4 for the
second alarm level. There is optional zone isolation
alarm relay (K5 & K6) for each Sensor. The Control
Module can be located in the area to be monitored, or in
a separate location, typically outside of the monitored
room.
Monitoring Points
Each monitoring point consists of an
analog signal generating sensor connected to the control
module via discrete, three conductor cable. Each sensor
can be mounted up to 1000 feet away in locations where
leaked refrigerant is likely to concentrate.
The Sherlock gas sensors are
available in three varieties:
Ceramic Metal Oxide Semiconductor
(CMOS) or Solid State Sensor
Non-Dispersive, Pyro-Electric
Infrared Sensor.
Oxygen Depletion Electro-chemical
Sensor.
Alarm Level Settings
The Sherlock 102 allows you to
set a unique Level 1 Alarm Setpoint and delay and Level
2 Alarm Setpoint and delay for each individual sensor.
When an Alarm Setpoint is exceeded, after the user set
delay, corresponding alarm relays are activated Each
Alarm Setpoint has a programmable Alarm Delay, 1 to 120
minutes. Sensor readings are required to exceed an Alarm
Setpoint for the programmed amount of time before the
control activates the corresponding alarm relay
contacts. For example, if the Alarm Setpoint is 200 and
the Alarm Delay is five minutes, the control will enter
an alarm condition only if the sensor detects a level of
200 or higher for more than five minutes.
Alarm Indication
All alarms are logged to indicate
which sensor went in and out of any of the two alarm
levels, the time and date of the alarm. The alarm log
stores the last 10 alarms. When a sensor is in alarm, a
red alarm light on the front panel will flash and the
on-board beeper will sound and the display will show the
activated alarm level.
Alarm Relay Contacts
The Sherlock 102 provides two
fused SPDT (Single Pole Double Throw) relay outputs for
each alarm level that switch positions in the event of
an alarm condition. Level 1 Alarm activates K1 and K2
relays. Level 2 Alarm activates K3 and K4 relays. Level
2 alarm on each individual sensor can be disabled. One
alarm relay on each level (K2/K4) can be silenced
(returned to non-alarm state) when the ALARM CLEAR
button on the front panel is pushed. The other alarm
relays will remain active until the alarm condition is
cleared. The Sherlock 102 can be programmed so
that the alarm is cleared automatically when the air is
cleared below the alarm setpoint (UNLATCHED) The relays
can also be programmed so the alarm is latched "ON"
until the alarm is manually reset. The relays can be
configured so the relays are "Energized to Alarm" (where
the C-NC contacts open on alarm) or "De-Energized to
Alarm" (where the relay is energized during normal
operations and the C-NC contacts close on alarm).
Systems Sensor
Opening Monitoring
The Sherlock 102 constantly
monitors the wiring to the sensors. Should any of the
activated sensor wires be cut or disconnected, "SENSOR
ALARM" will appear on the SHERLOCK display, the K1 and
K2 relays will be activated and the condition is logged.
Setback Alarm
Settings
In some locations the sensor may be
expected to function in two different environments. For
example, the sensor may have to perform in still air
(i.e. with the exhaust fan off) and in moving air ( i.e.
with the exhaust fan on), or the sensor may be used in a
location where changes in air quality, perhaps caused by
the use of propane powered floor buffers, elevates the
sensor readings. The Sherlock 102 provides a
feature called SETBACK to accommodate alternate
environments under which the sensor would operate.
SETBACK provides a second ALARM SETPOINT and a second
ALARM DELAY enabling the sensor to perform in this
second environment. The Sherlock 102
switches to the second set of parameters when a dry
contact (i.e. air flow switch, sail switch or timer
switch) closes or on a daily time schedule.