Product Categories

Refrigerant Gas Monitoring Panels - Fixed Systems

Refrigerant Gas Monitoring - Portable Systems

Compressor Condensing Unit Control Panels

Condenser Control Panels

Evaporator - Room - Zone Control Panels

Air-Handler, Chiller, and Energy Management Control Panels

Sensors

Breathing Apparatus and Accessories

Alarm Indication Equipment

Remote Monitoring and Communications

OEM - Original Manufactured Equipment

SHERLOCK 402 Refrigerant Gas Monitoring System

  

 

 

 

 MODEL       NEMA/IP     ELECTRICAL      POLLUTION

      #            RATING      CATEGORY       PROTECTION

    402                1                  II                          2

  402-4          4X/IP67             II                          3

 402-PM             1                  II                          2

 

NEMA 1 Compliant Enclosure - This enclosure is intended for indoor use only primarily to provide a degree of protection against contact with the enclosed equipment. The enclosure is not designed to provide protection from water or to be placed in a hazardous environment. Mount only in Pollution Level 2 environments, ie. environmentally controlled offices, control rooms, or environmentally controlled machine rooms.

DIMENSIONS    12"H x 9.25"W x 5.25"D Nema 1

 

NEMA 4X Compliant Enclosure - This enclosure is intended for either indoor or outdoor use, 0 to 50 °C, to provide a degree of protection against corrosion, windblown dust and rain, splashing water, and hose directed water.

DIMENSIONS    14"H x 12"D x 7"D Nema 4X

 

NEMA 1 Panel Mount Option - The control and display assemblies must be suitably mounted in an enclosure. The Faceplate may be surface mounted onto a Nema 1 enclosure. The IO Board Assembly must be mounted within an enclosure providing at least Nema 1 protection.

DIMENSIONS    10.2"H x 8.5" W x 2"D PM Faceplate

                         10.6"H x 8.5"W x 3"D PM Backplate

 

POWER             90 to 250VAC, 50/60 Hz, 1.0 Amps

INPUTS             Four (4) SHERLOCK sensor Cmos or IR 

                                or

                         Three (3) SHERLOCK sensor Cmos or IR

                         One Oxygen Depletion Sensor

                         Two dry contacts -- Setback 1 / Setback 2

OUTPUTS          Four SPDT, 1 Form C relays 250VAC, 3.15Amp Slo-Blo fuse

                        

                         Optional Zone Isolation Relays - Four SPDT, 1 Form C relays 250VAC, 3.15Amp Slo-Blo fuse

 

OPERATING TEMPERATURE     45ºF - 99ºF

OPERATING HUMIDITY             30% - 90% RH, non- condensing

ALARMS             Two Alarm Levels, two SPDT Relays per level.

                               One Silenceable when in alarm

                           Optional One (1) Zone Isolation alarm relay per each sensor.

DISPLAY             2 lines by 20 characters Alphanumeric LCD with back light

                           Alarm Indication LED -- indicates active alarm

                           

KEYPAD              5 tactile key switches:  Scroll up, Scroll down, Select/Change, Exit, Alarm Silence/Clear

ALARM INDICATORS

      LCD DISPLAY    Name, description, and current reading of alarming sensor

      BUZZER            Piezo-electric, 90db @10ft, silenceable

      STATUS LED     Four on front panel of control. Indicates alarm status of each sensor

      STROBE LIGHT (Optional)       Mounted on top of the housing, activates during any alarm condition.

 

Genesis International, Inc. reserves the right to change product specifications and availability without notice.

Contact a factory representative for additional information on this and any other products.