|
Monitoring Panel
The Sherlock 802 Control
Module is a hard wired, electronic control panel that is
capable of monitoring the analog output signal of up to
eight Sherlock Refrigerant Gas Sensors or seven
Sherlock Refrigerant Gas Sensors and one
Sherlock Oxygen Depletion Sensors and two digital
dry-contact switches. The Control Module will activate
four Form C SPDT relay contacts based upon the
programmed alarm setpoints of each sensor. The relays
are referred to as K1A, K1B for the first alarm level
and K2A, K2B for the second alarm level. There is
optional zone isolation alarm relay (A-H) for each
Sensor. The Control Module can be located in the area to
be monitored, or in a separate location, typically
outside of the monitored room.
Monitoring Points
Each monitoring point consists of an
analog signal generating sensor connected to the control
module via discrete, three conductor cable. Each sensor
can be mounted up to 800 feet (longer run with special
cable) away in locations where leaked refrigerant is
likely to concentrate.
The gas sensors are available in
three varieties:
Ceramic Metal Oxide Semiconductor
(CMOS) or Solid State Sensor
Non-Dispursive, Pyro-Electric
Infrared Sensor.
Oxygen Depletion Electro-chemical
Sensor.
Alarm Level Settings
The Sherlock 802 allows you to
set a unique Level 1 Alarm Setpoint and Level 2 Alarm
Setpoint for each individual sensor. When an Alarm
Setpoint is exceeded, corresponding alarm relays are
activated Each Alarm Setpoint has a programmable Alarm
Delay, 1 to 120 minutes. Sensor readings are required to
exceed an Alarm Setpoint for the programmed amount of
time before the control activates the corresponding
alarm relay contacts. For example, if the Alarm Setpoint
is 200 and the Alarm Delay is five minutes, the control
will enter an alarm condition only if the sensor detects
a level of 200 or higher for more than five minutes.
Alarm Indication
All alarms are logged to indicate
which sensor went in and out of any of the two alarm
levels, the time and date of the alarm. The alarm log
stores the last 32 alarms. When a sensor is in alarm, an
alarm LED for this sensor on the front panel will turn
to red color, the on-board beeper will be beeping and
the display will show the activated alarm level.
Alarm Relay Contacts
The Sherlock 802 provides two
fused SPDT (Single Pole Double Throw) relay outputs for
each alarm level that switch positions in the event of
an alarm condition. Level 1 Alarm activates K1A and K1B
relays. Level 2 Alarm activates K2A and K2B relays.
Level 2 alarm on each individual sensor can be disabled.
One alarm relay on each level (K1B/K2B) can be silenced
(returned to non-alarm state) when the SILENT button on
the front panel is pushed. The other alarm relay will
remain active until the alarm condition is cleared. The
Sherlock 802 can be programmed so that the alarm
is cleared automatically when the air is cleared below
the alarm setpoint (UNLATCHED) The relays can also be
programmed so the alarm is latched "ON" until the alarm
is manually reset. The K1/K2 alarm level can be
configured so the relays are "Energized to Alarm" (where
the C-NC contacts open on alarm) or "De-Energized to
Alarm" (where the relay is energized during normal
operations and the C-NC contacts close on alarm).
Optional zone isolation alarm relay(A-H) for each sensor
can be programmed to activate by level 1 or level 1&2
alarm.
Zone Isolation Alarm
Relays (Optional)
An optional Zone Isolation Relay Kit
is available for the Sherlock 801. This kit allows
the user to directly control or activated alarm
circuitry specific to each sensor. This circuitry
can include Audio / Visual alarm appliances mounted
within the location where each sensor is located.
The relays can be used to shutdown refrigeration or
mechanical equipment within room where each sensor is
located.
Sensor Failure
Monitoring
The Sherlock 802 constantly
monitors the wiring to the sensors. Should any of the
activated sensor wires be cut or disconnected, "OPEN"
will appear on the SHERLOCK display, the K1A and K1B
relays will be activated and the condition is logged.
Setback Alarm
Settings
In some locations the sensor may be
expected to function in two different environments. For
example, the sensor may have to perform in still air
(i.e. with the exhaust fan off) and in moving air ( i.e.
with the exhaust fan on), or the sensor may be used in a
location where changes in air quality, perhaps caused by
the use of propane powered floor buffers, elevates the
sensor readings. The Sherlock 802 provides a
feature called SETBACK to accommodate alternate
environments under which the sensor would operate.
SETBACK provides a second ALARM SETPOINT and a second
ALARM DELAY enabling the sensor to perform in this
second environment. The Sherlock 802 switches to
the second set of parameters when a dry contact (i.e.
air flow, sail switch or timer) closes or on a daily
time schedule.
Each sensor can be programmed with
one of five SETBACK options:
1) No SETBACK
2) SETBACK triggered by setback
input 1 and the Setback Clock
3) SETBACK triggered by setback
input 2 only
Each sensor can be programmed with
only one SETBACK option; however, different sensors may
be programmed to follow different options. |