The Sherlock 804
Control Module is a hardwired, electronic control panel
that is capable of monitoring the analog output signal
of up to four Sherlock Refrigerant Gas
Sensor or Sherlock Oxygen Depletion
Sensors and four digital dry-contact switches. The
Control Module can activate eight, Form C SPDT relay
contacts based upon the programmed alarm level setpoint
levels of each sensor. The Control Module can be located
in the area to be monitored, or in a separate location,
typically outside of the monitored room.
Monitoring Points
Each monitoring point consists of an
analog signal generating sensor connected to the control
module via discrete, three conductor cable. Each sensor
can be mounted up to 800 feet away in locations where
leaked refrigerant is likely to concentrate.
The gas sensors are available in four
varieties:
Ceramic Metal Oxide Semiconductor
(CMOS) or Solid State Sensor
Non-Dispursive, Pyro-Electric
Infrared Sensor.
Oxygen Depletion Electro-chemical
Sensor.
Electrochemical Sensor
Alarm Level Settings
The Sherlock 804 allows you to set
three unique Alarm Setpoints for each individual
sensor throughout their operating. When an Alarm
Setpoint is exceeded, a corresponding set of alarm
relays are activated Each Alarm Setpoint has a
programable Alarm Delay, 1 to 120 minutes. Sensor
readings are required to exceed an Alarm Setpoint for
the programmed amount of time before the control
activates the corresponding alarm relay contacts. For
example, if the Alarm Setpoint is 200 and the
Alarm Delay is five minutes, the control will enter
an alarm condition only if the sensor detects a level of
200 or higher for more than five minutes.
Alarm level #1 and Alarm Level #2 on
every sensor has the option of using the Time Weighted
Average (TWA) reading as the input reading. Time
Weighted Average reading of a sensor is the average
reading of a sensor input over a period of time.
Alarm Indication
All alarms are logged to indicate
which sensor went in and out of any of the three alarm
levels, the time and date of the alarm. The alarm log
stores the last 32 alarms. When a sensor is in alarm, an
LED on the front panel will turn to red color, the
on-board beeper will be beeping and the display will go
into "IN ALARM" screen every five seconds. The
individual sensor causing the alarm also displays the
"ALARM" message.
Alarm Relay Contacts
The Sherlock 804 provides two fused SPDT (Single Pole Double Throw) relay outputs for each
alarm level that switch positions in the event of an
alarm condition. The ‘B’ relay for each alarm level can
be temporarily or permanently silenced by pushing the
respective alarm silence button on the front panel. The
relay will re-activate after a programmed period of
time, if the alarm condition is not cleared. The ‘A’
relay however will remain active until the alarm
condition is cleared. The Sherlock 804 can be programmed
so that the alarm is cleared automatically when the air
is cleared below the alarm setpoint (UNLATCHED) It can
also be programmed so the alarm is latched "ON" until
the alarm is manually reset. Each alarm level can be
configured so the relays are "Energized to Alarm" (where
the C-NC contacts open on alarm) or "De-Energized to
Alarm" (where the relay is energized during normal
operations and the C-NC contacts close on alarm).
Analog Signal
Generator (Optional)
Sherlock 804 has an optional 0-5 V /
0-10 V / 4-20 mA analog output for each sensor. Either
of these signals can be incorporated to any commercially
used monitoring and alarming system or in-house Data
Management System.
Zone Isolation Alarm
Relays (Optional)
An optional Zone Isolation Relay Kit
is available for the Sherlock 804. This kit allows
the user to directly control or activated alarm
circuitry specific to each sensor. This circuitry
can include Audio / Visual alarm appliances mounted
within the location where each sensor is located.
The relays can be used to shutdown refrigeration or
mechanical equipment within room where each sensor is
located.
Systems Fault
Monitoring
The Sherlock 804 constantly monitors
the wiring to the sensors. Should any of the activated
sensor wires be cut or disconnected, "OPEN" will appear
on the SHERLOCK display, the alarm #1 and system alarm
are activated and the condition is logged. In addition
to the three alarm levels the Sherlock 804 is
also equipped with a SYSTEM FAULT ALARM. This alarm is
triggered when the system malfunctions (i.e. The sensor
wire is cut or inter-connect cable is cut).
Setback Alarm
Settings
In some locations the sensor may be
expected to function in two different environments. For
example, the sensor may have to perform in still air
(i.e. with the exhaust fan off) and in moving air ( i.e.
with the exhaust fan on), or the sensor may be used in a
location where changes in air quality, perhaps caused by
the use of propane powered floor buffers, elevates the
sensor readings. The SHERLOCK 804 provides a
feature called SETBACK to accommodate alternate
environments under which the sensor would operate.
SETBACK provides a second ALARM SETPOINT and a second
ALARM DELAY enabling the sensor to perform in this
second environment. The SHERLOCK 804
switches to the second set of parameters when a dry
contact (i.e. air flow, sail switch or timer) closes or
on a daily time schedule.
Each sensor can be programmed with
one of five SETBACK options:
1) No SETBACK
2) SETBACK triggered by setback
input 1 only
3) SETBACK triggered by setback
input 2 only
4) SETBACK triggered by setback
input 1 or the setback time clock
5) SETBACK triggered by the
setback time clock only
Each sensor can be programmed with
only one SETBACK option; however, different sensors may
be programmed to follow different options.