Infrared Refrigerant Gas Sensor

  • Sensor should be placed in the sensing area. No plastic tubing or air pumping is needed.

General

SHERLOCK NON-DISPERSIVE IR REFRIGERANT GAS SENSOR was designed to detect for the presence of certain refrigerant gases within an enclosed space.  The sensor is mounted within the space to be monitored and connected by cable to the monitoring device.  Each sensor is calibrated to monitor for a specific refrigerant gas. 

The IR Sensor is a reliable method of monitoring for refrigerant gas leaks in environments that have air quality problems. The IR sensor will eliminate many false alarms in environments that contain gasoline, diesel, and propane exhaust and fumes from solvents, paints, cleansers, and others. (Please call Genesis Customer Support for more information).

Specifications

ENCLOSURE           NEMA 3R Short     8.25"x 4.75"x 2.5"

                               NEMA 3R Long     11.0"x 4.75"x 2.5"

POWER INPUT        12VDC, 400 mAMPs

OUTPUTS                0 to 20ma/4 to 20ma (Jumper selectable) 

RANGE                    0 to 1000 ppm

SENSITIVITY           ±1 ppm at 25 ° C, 45% RH

RESOLUTION          1 ppm

AVAILABLE GAS SENSORS

            R11                    R12                    R22

            R123                  R134A               R401A (MP39)

            R401B (MP62)  R404A (HP62)   R502

            R-507                R717 (AMMONIA)

OPERATING ENVIRONMENT

    TEMPERATURE               -40 to 120°F (-40 TO 50°C)

    HUMIDITY                         0 TO 85% RH Non-condensing

CALIBRATION                     Every 6 months

WARM-UP TIME                  Readings will stabilize after 3 hours.

Applications

Typical applications include:

            HVAC Chiller Equipment Rooms

            Refrigeration Mechanical Rooms

            Refrigerated Rooms

            Wineries

            Bakeries

            Food Processing Plants

 

Genesis International, Inc. reserves the right to change product specifications and availability without notice.

Contact a factory representative for additional information on this and any other products.